UPS PowerValue 11T G2 6 kVA

TECH SPECS
| GENERAL DATA | |
| Output rated power | 6.000 W |
| Output power factor | 1.0 |
| Topology | Online double conversion |
| Parallel configuration | Yes, up to 3 UPS |
| Inbuilt batteries | Yes/Yes/No |
| INPUT | |
| Nominal input voltage | 208/220/230/240 VAC |
| Input voltage tolerance | 100-276 (load dependent) |
| Input current THDi | <3% with full resistive load |
| Frequency range | 45-55Hz / 54-66Hz (extendable to 40~70HZ at load < 60%) |
| Power factor | ≥0.995 |
| OUTPUT | |
| Rated output voltage | 208/220/230/240 VAC |
| Voltage tolerance | ±1% (referred to 230V) |
| Voltage distortion | <1% linear load, <5% non linear load |
| Overload capacity (linear load) on inverter |
10m: 102-125% load 30s: 126 to 150% load 500 ms: ≥ 150% load |
| Nominal frequency | 50 or 60 Hz |
| Crest factor | 3:1 (load supported) |
| EFFICIENCY | |
| Overall system efficiency | Up to 95% |
| In eco-mode | Up to 98% |
| ENVIRONMENT | |
| Protection rating | IP20 |
| Storage temperature | UPS: -25°C to 60°C; Batteries: 0°C to 35°C |
| Operating temperature | 0°-40°C (up to 50°C at 50% load) |
| Relative humidity | 0% to 95% |
| Altitude (above see level) | 1000m without derating |
| BATTERIES | |
| Type | VRLA (valve regulated lead-acid) |
| Inbuilt batteries | 16x9Ah(B) |
| Charging current | 0-4A adjustable (B) |
| Recharge time (inbuilt batteries) | 4h to 90% |
| COMMUNICATIONS | |
| User interface | LCD display |
| Optional communication cards | SNMP; ModBus; AS400; Environmental monitoring sensor probe |
| STANDARDS | |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Performance | IEC/EN 62040-3 |
| Manufacturing | ISO 9001:2015, ISO 14001:2015, OHSAS 18001 |
| WEIGHT, DIMENSIONS | |
| Weight | 53/63/13 Kg |
| Dimensions w x h x d | 225 x 589x 452 mm |





Reviews